Portable fire extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3
[ "authority", "obligation" ]
nfpa-10-2010-ed-annual-maintenance-portable-fire-extinguishers
at least once a year
Annual maintenance
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
“Maintenance” is a thorough examination and repair, as needed, of your facility’s portable fire extinguishers and is covered in NFPA 10(10), Sec. 7.3. Maintenance is required at least once a year – more frequently when indicated by a routine monthly inspection, as discussed earlier.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-annual-maintenance-portable-fire-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Carbon dioxide
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-carbon-dioxide
every 5 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-carbon-dioxide/
[ "agent_type", "citation", "interval" ]
null
Dry chemical extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-dry-chemical-extinguishers
every 12 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years o Dry chemical extin...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-dry-chemical-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Nonrechargeable stored pressure extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.2.1.3
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-nonrechargeable-stored-pressure-extinguishers
removed from service 12 years from the date of manufacture
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
As mentioned earlier, the exception to the rule for hydrostatic testing is nonrechargeable stored pressure extinguishers (e.g. dry chemical extinguishers), which are required to be removed from service 12 years from the date of manufacture [see NFPA 10(10), Sec. 7.3.1.2.1.3].
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-nonrechargeable-stored-pressure-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Pressurized water
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-pressurized-water
every 5 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-pressurized-water/
[ "agent_type", "citation", "interval" ]
null
Dry chemical extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-stainless-steel-shells-dry-chemical-extinguishers
every 5 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years o Dry chemical extin...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-stainless-steel-shells-dry-chemical-extinguishers/
[ "agent_type", "citation", "interval", "shell_material" ]
stainless steel shells
Water mist
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-water-mist
every 5 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-water-mist/
[ "agent_type", "citation", "interval" ]
null
Wet chemical (e.g. K-type)
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 8.3.1 and Table 8.3.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-hydrostatic-test-wet-chemical-e-g-k-type
every 5 years
Hydrostatic test
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Hydrostatic testing intervals for fire extinguishers are outlined in NFPA 10(10), Sec. 8.3.1 and Table 8.3.1. Test intervals for some of the most commonly found extinguishers are as follows: o Pressurized water, water mist, carbon dioxide and wet chemical (e.g. K-type) extinguishers – every 5 years
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-hydrostatic-test-wet-chemical-e-g-k-type/
[ "agent_type", "citation", "interval" ]
null
Antifreeze type extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-antifreeze-type-extinguishers
annually
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-antifreeze-type-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Carbon dioxide
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-carbon-dioxide
every 5 years
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. Car...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-carbon-dioxide/
[ "agent_type", "citation", "interval" ]
null
Dry chemical extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-dry-chemical-extinguishers
Every 6 years
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Every 6 years, stored pressure fire extinguishers that require a 12-year hydrostatic test (e.g. dry chemical extinguishers) must be emptied and subjected to an internal examination by a trained technician in accordance with procedures detailed in the manufacturer’s service manual and NFPA 10(10), Sec. 7.3.1.2.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-dry-chemical-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Nonrechargeable extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.2.1.3
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-nonrechargeable-extinguishers
removed from service 12 years from the date of manufacture
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
The exception to this rule is nonrechargeable extinguishers, which are required to be removed from service 12 years from the date of manufacture [see NFPA 10(10), Sec. 7.3.1.2.1.3].
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-nonrechargeable-extinguishers/
[ "agent_type", "citation", "interval" ]
null
Stored pressure fire extinguishers that require a 12-year hydrostatic test
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-stored-pressure-fire-extinguishers-that-require-a-12-year-hydrostatic-test
Every 6 years
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Every 6 years, stored pressure fire extinguishers that require a 12-year hydrostatic test (e.g. dry chemical extinguishers) must be emptied and subjected to an internal examination by a trained technician in accordance with procedures detailed in the manufacturer’s service manual and NFPA 10(10), Sec. 7.3.1.2.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-stored-pressure-fire-extinguishers-that-require-a-12-year-hydrostatic-test/
[ "agent_type", "citation", "interval" ]
null
Stored-pressure loaded-stream
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-stored-pressure-loaded-stream
annually
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-stored-pressure-loaded-stream/
[ "agent_type", "citation", "interval" ]
null
Wet chemical (e.g. K-type)
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2
[ "authority", "obligation" ]
nfpa-10-2010-ed-internal-examination-wet-chemical-e-g-k-type
every 5 years
Internal examination
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
It must be noted that some types of extinguishers are required to undergo an internal examination at more frequent intervals as specified in NFPA 10(10), Sec. 7.3.1.1.2 and Table 7.3.1.1.2. For example, stored-pressure loaded-stream and antifreeze type extinguishers are required to be internally inspected annually. Car...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-internal-examination-wet-chemical-e-g-k-type/
[ "agent_type", "citation", "interval" ]
null
Portable fire extinguishers
NFPA 10 (2010 ed.)
NFPA 10(10), Sec. 7.2.1
[ "authority", "obligation" ]
nfpa-10-2010-ed-monthly-visual-inspection-portable-fire-extinguishers
at least monthly at a minimum of 30-day intervals
Monthly visual inspection
https://www.health.state.mn.us/facilities/regulation/engineering/docs/lscfireext.pdf
Portable fire extinguishers are required to be visually inspected when initially placed in service and at least monthly at a minimum of 30-day intervals thereafter [see NFPA 10(10), Sec. 7.2.1].
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/nfpa-10-2010-ed-monthly-visual-inspection-portable-fire-extinguishers/
[ "agent_type", "citation", "interval" ]
null
portable fire extinguishers
OSHA 29 CFR 1910.157
null
[ "authority", "obligation" ]
osha-29-cfr-1910-157-annual-maintenance-portable-fire-extinguishers
annual maintenance check
Annual maintenance
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable fire extinguishers are subjected to an annual maintenance check. Stored pressure extinguishers do not require an internal examination. The employer shall record the annual maintenance date and retain this record for one year after the last entry or the life of the shell, whicheve...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-annual-maintenance-portable-fire-extinguishers/
[ "agent_type", "interval" ]
null
Aqueous Film Forming foam (AFFF)
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-aqueous-film-forming-foam-afff
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-aqueous-film-forming-foam-afff/
[ "agent_type", "citation", "interval" ]
null
Carbon dioxide
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-carbon-dioxide
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-carbon-dioxide/
[ "agent_type", "citation", "interval" ]
null
Cartridge operated water and/or antifreeze
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-cartridge-operated-water-and-or-antifreeze
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-cartridge-operated-water-and-or-antifreeze/
[ "agent_type", "citation", "interval" ]
null
Halon 1211
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-halon-1211
12
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-halon-1211/
[ "agent_type", "citation", "interval" ]
null
Halon 1301
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-halon-1301
12
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-halon-1301/
[ "agent_type", "citation", "interval" ]
null
Loaded stream
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-loaded-stream
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-loaded-stream/
[ "agent_type", "citation", "interval" ]
null
Dry chemical, stored pressure
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-mild-steel-brazed-brass-or-aluminum-shells-dry-chemical-stored-pressure
12
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-brazed-brass-or-aluminum-shells-dry-chemical-stored-pressure/
[ "agent_type", "citation", "interval", "shell_material" ]
mild steel, brazed brass or aluminum shells
Dry chemical, cartridge or cylinder operated
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-chemical-cartridge-or-cylinder-operated
12
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-chemical-cartridge-or-cylinder-operated/
[ "agent_type", "citation", "interval", "shell_material" ]
mild steel shells
Dry powder, cartridge or cylinder operated
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-powder-cartridge-or-cylinder-operated
12
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-mild-steel-shells-dry-powder-cartridge-or-cylinder-operated/
[ "agent_type", "citation", "interval", "shell_material" ]
mild steel shells
Dry chemical
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-dry-chemical
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-dry-chemical/
[ "agent_type", "citation", "interval", "shell_material" ]
stainless steel
Foam
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-foam
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-foam/
[ "agent_type", "citation", "interval", "shell_material" ]
stainless steel shell
Soda acid
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-soda-acid
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stainless-steel-shell-soda-acid/
[ "agent_type", "citation", "interval", "shell_material" ]
stainless steel shell
Stored pressure water and/or antifreeze
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-stored-pressure-water-and-or-antifreeze
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-stored-pressure-water-and-or-antifreeze/
[ "agent_type", "citation", "interval" ]
null
Wetting agent
OSHA 29 CFR 1910.157
Table L-1
[ "authority", "obligation" ]
osha-29-cfr-1910-157-hydrostatic-test-wetting-agent
5
Hydrostatic test
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that portable extinguishers are hydrostatically tested at the intervals listed in Table L-1 of this section, except under any of the following conditions: ( i ) When the unit has been repaired by soldering, welding, brazing, or use of patching compounds; ( ii ) When the cylinder or shell threa...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-hydrostatic-test-wetting-agent/
[ "agent_type", "citation", "interval" ]
null
Dry chemical extinguishers having non-refillable disposable containers
OSHA 29 CFR 1910.157
null
[ "authority", "obligation" ]
osha-29-cfr-1910-157-internal-examination-dry-chemical-extinguishers-having-non-refillable-disposable-containers
exempt from this requirement
Internal examination
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and subjected to applicable maintenance procedures every 6 years. Dry chemical extinguishers having non-refillable disposable containers are exempt from this requirement. When recharging or hydr...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-internal-examination-dry-chemical-extinguishers-having-non-refillable-disposable-containers/
[ "agent_type", "interval" ]
null
stored pressure dry chemical extinguishers that require a 12-year hydrostatic test
OSHA 29 CFR 1910.157
null
[ "authority", "obligation" ]
osha-29-cfr-1910-157-internal-examination-stored-pressure-dry-chemical-extinguishers-that-require-a-12-year-hydrostatic-te
every 6 years
Internal examination
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
The employer shall assure that stored pressure dry chemical extinguishers that require a 12-year hydrostatic test are emptied and subjected to applicable maintenance procedures every 6 years. Dry chemical extinguishers having non-refillable disposable containers are exempt from this requirement. When recharging or hydr...
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-internal-examination-stored-pressure-dry-chemical-extinguishers-that-require-a-12-year-hydrostatic-te/
[ "agent_type", "interval" ]
null
Portable extinguishers
OSHA 29 CFR 1910.157
null
[ "authority", "obligation" ]
osha-29-cfr-1910-157-monthly-visual-inspection-portable-extinguishers
monthly
Monthly visual inspection
https://www.ecfr.gov/current/title-29/subtitle-B/chapter-XVII/part-1910/subpart-L/section-1910.157
Portable extinguishers or hose used in lieu thereof under <https://www.ecfr.gov/current/title-29/section-1910.157#p-1910.157(d)(3)> paragraph (d)(3) of this section shall be visually inspected monthly.
https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/osha-29-cfr-1910-157-monthly-visual-inspection-portable-extinguishers/
[ "agent_type", "interval" ]
null

Fire extinguisher inspection, maintenance and hydrostatic test intervals by agent type

Canonical, always-current version: https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/ Machine-readable: https://referencesource.org/fire-extinguisher-inspection-testing-intervals-by-type/data.json — this mirror is a point-in-time copy.

  • Last verified: 2026-08-19
  • Stale after: 2027-08-19 (past this date, prefer the canonical copy — it re-verifies on a cadence this snapshot does not)
  • Records: 34

NFPA 10 sets four separate service obligations for a portable fire extinguisher (monthly visual inspection, annual maintenance, periodic internal examination, and hydrostatic pressure testing) and the interval for two of those four depends on which agent and shell the extinguisher is, in a way that is scattered across several sections and a table rather than stated as one list. A record here is one obligation for one extinguisher type/shell combination, with the interval and the NFPA 10 section it comes from. Answers 'how often does a CO2 extinguisher need hydrostatic testing', 'does a stainless steel dry chemical extinguisher get the same 12-year hydro interval as a standard one', 'how often does a wet chemical K-class extinguisher need internal examination', and 'my dry chemical extinguisher is nonrechargeable, when does it get replaced instead of retested'. The exceptions are where a facility manager gets this wrong: stainless steel dry chemical shells get the 5-year interval that pressurized-water and CO2 units get, not the 12-year interval every other dry chemical extinguisher gets, and nonrechargeable stored-pressure extinguishers skip hydrostatic testing entirely in favor of a hard 12-year removal-from-service date. Two authorities are carried side by side, because a US workplace is answerable to both and they are not word-for-word identical: NFPA 10, as restated for regulated facilities by the Minnesota Department of Health, and OSHA's own general-industry standard at 29 CFR 1910.157, whose Table L-1 sets hydrostatic intervals directly in regulation and names types the NFPA summary does not (foam, AFFF, Halon 1211 and 1301, dry powder, wetting agent). Where the two overlap they agree, and each row says which rulebook it answers to.

Provenance — what every record carries

Every record carries source (the URL the value was read from) and source_quote (a verbatim quote from that page stating it). A value you cannot check against its page is indistinguishable from an invented one; these can all be checked. Each record is also individually addressable on the canonical site at its url.

Licence position

NFPA 10 is a copyrighted, sold standard; the facts (which interval applies to which extinguisher type) are not themselves copyrightable and are already restated by every state health/fire authority that regulates against it. This asset never reproduces the standard's text. The NFPA-derived rows take the interval and its qualifier from a Minnesota Department of Health guidance document that already restates NFPA 10's requirements for its regulated facilities, quote a short verbatim span, and cite the specific NFPA 10 section. The OSHA rows are taken from 29 CFR 1910.157, which is a US government work in the public domain and states its own intervals in Table L-1 rather than incorporating NFPA 10 by reference.